air outlets |  Ceiling Diffuser

Disc Valves

Construction

1- Frame and disc

Steel sheet construction.

2- Mounting rings

Galvanized sheet steel.

① Valve disc

② Valve casing

③ Cross bar

④ Threaded spindle with lock nut

Description 

Frame and disc is made of high quality galvanized steel sheet construction with powder coating to RAL colors.

Disc is attached to the frame by threaded rod.

Air flow can be adjusted by regulating the cone up or down (+A or -A).

Foam gasket is sealed around the back of the frame to avoid air leakage.

These valves can be used for supply, exhaust and ventilation applications.

Air master disc valves are best suited to air distribution systems handling relatively low air flow rates within small circular duct work.

Can be mounted in wall, ceiling or exposed air ducts with mounting rings.

Recommended for exhaust of greasy and damp air in damp areas such as toilets, bathrooms and kitchens.

Standard finishes Steel sheet powder coated to RAL 9010 color.

Flexibility of finishing is available as option.

Standard sizes :

Fixing details

Direct fixing into the duct with mounting rings.

First mounting ring has to be fixed into the duct outlet before the valve is pushed into the ring.

Technical Data

Application

Type DV disc valves are used as extract air devices in small rooms.

For variable and constant volume flows.

For walls and suspended ceilings.

Special characteristics

Continuous volume flow rate balancing by turning the valve disc.

Easy to install.

Nominal sizes

100, 125, 160, 200.

Parts and characteristics

Valve disc with threaded spindle and lock nut.

Valve casing including cross bar with orifice for the threaded spindle.

Installation sub frame that accommodates the disc valve.

Materials and surfacesValve casing and valve disc made of galvanized sheet steel.

Installation sub frame, cross bar, threaded spindle and lock nut made of galvanized steel.

Foam seal.

Valve casing and valve disc powder-coated RAL 9010, pure white.

Standards and guidelines

Sound power level of the air-regenerated noise measured according to EN ISO 5135.

Maintenance

Maintenance-free as construction and materials are not subject to wear.

Inspection and cleaning to VDI 6022.

Technical Data

Table 9.2(A) Air flow data Supply air disc valve

Pt = Total pressure loss across the disc valve in mm of H2O.

NC based on a room attenuation of 10 dB.

A = +10,0 & -10 = Position of the disc 10 mm down of normal position, at normal position, and 10 mm above normal posits

Technical Data

Table 9.2(B) Air flow data Return air disc valve

Pt = Total pressure loss across the disc valve in mm of H2O.

NC based on a room attenuation of 10 dB.

A = +10,0 & -10 = Position of the disc 10 mm down of normal position, at normal position, and 10 mm above normal position.

Technical Data

Quick SizingQuick sizing tables provide a good overview of the volume flow rates and corresponding sound power levels and differential pressures.

DV/100, DV /125, sound power level and total differential pressure

DV /160, sound power level and total differential pressure

DV /200, sound power level and total differential pressure

Sizing example

Given data

V = 25 l/s (90 m3/h)

Extract air valve

Maximum sound power level 30 dB(A)

Quick sizing

Type DV

Selectable nominal sizes: 125, 160, 200

Selected: DV/125

Technical Data

Dimensions and weight

Technical Data

Installation details Installation and commissioning

Installation flush with the wall or ceiling.

Perform volume flow rate balancing by turning the valve disc, then tighten the lock nut to fix the valve disc in the required position.

These are only schematic diagrams to illustrate installation details.

Installation flush with the wall or ceiling, with installation sub frame

Performance Data

Table 9.1 Supply air valves Vs Throw in meters (A = 0)

Note

For position A = +10, reduce throw by 30%.

For position A=-10, increase throw by 40%.

How to order